Single Phase 2 Wire Neutral Missing Tamper proof Meter
1,Summary
DDSXXX Single Phase 2 Wire Neutral Missing Tamper proof Meter adpots advanced low powe rconsumption solid PCB technology and SMT advanced craft used for count single phase frequency 50Hz AC active energy.
2,Function and feature
2.1 Measure electric energy precision is stable. Meters don’t need adjust after ex-work. It does prolong inspection circle and lower grid department’s job of test and calibration meters.
2.2 It can register bi-directionally, count forward, and reverse direction active energy, reverse energy count into forward.
2.3 It has current active demand measure funtion, meter display current demand. Demand display is 0 when power off, live wire disconnects and neutral wire disconnect.
2.4 Energy meter with tamper proof, measured as per bigger one when two wire current unbanlanced, measured as per reference voltage and actual wire current (when wire current more than 1A) when live wire or neutral wire disconnect.
2.5 It adopts optical isolation no source impulse output port.
2.6 LCD display energy value and current demand data always including power off.
2.7 LED indcate situation of energy, impulse indicator: indicator flashing as per load when current through current, flash speed in proportion to
Load; reverse indicator: Indicators light when detected reverse current, indicator off when current recover to forward, indicator off and don’t detect current direction when live wire or neutral wire disconnect; tamper indicator: indicator light when detected L and N current unbalanced when voltage work normaly, indicator off when L and N current recover to balanced, indicator light 1s and off 2s flashing in turn when detected L or N disconnected (The current of L or N wire more than 1A)
3, Specification and main parameter
3.1 Main type
Type | Class | Reference voltage Un | Rated current |
DDSXXX | 1
| 230V | 3×5(30)A 3×10(60)A 3×20(100)A
|
3.2 Basic error
Load current | Power factor | Basic error(%)
|
0.05Ib | 1.0 | ±1.5 |
0.1Ib~Imax | 1.0 | ±1.0 |
0.1Ib | 0.5(L) | ±1.5 |
0.8(C) | ±1.5 | |
0.2Ib~Imax | 0.5(L) | ±1.0 |
0.8(C) | ±1.0 |
Ib is basic current Imax is max current
3.3 Starting: Under the conditions of rated voltage and rated power factor is 1.0, the meter will constantly count electricity when loaded current of the meter is 0.4%Ib(Class 1).
3.4 Running with no-load:Meter with anti running with no-road circuit. Meter test output less than 1 impulse when the circuit of the meter has no electric load but has 115% reference voltage.
3.5 Power losses:≤1.5W(5VA).
3.6 Environment situation
Standard work temperature:-25°C~55°C
Limit work temperature :-40°C~70°C